#1 India's Top IT Training Institute
×

About Uncodemy

Know more about who we are and what we stand for.

About Us

About Us

Discover our mission to equip individuals with essential IT skills and industry expertise.

Read More →
UnCodeMy Gallery

UnCodeMy Gallery

Explore highlights from our IT training sessions and success stories.

Read More →
Mentors

Mentors

Meet the industry experts who train and guide you through your course.

Read More →
Free Resources

Free Resources

Free tutorials, interview questions, tools and calculators to help you learn.

Explore →
×

Free Resources

Learn, practice and plan your career — bilkul free.

Tutorials

Tutorials

Step-by-step written tutorials to learn any technology at your own pace.

Read More →
Free Counselling

Free Counselling

Book a free video counselling session and pick the right course for you.

Read More →
Online Compiler

Online Compiler

Write, run and test your code online — no setup required.

Read More →
⚡ FREE · 7 EXCHANGER TYPES

NTU-Effectiveness Calculator: Heat Exchanger Rating and Sizing

ε-NTU method for 7 exchanger types: find outlet temperatures or the area needed.

  • 🔁 Rating and sizing
  • 📊 ε, NTU, Cr and Qmax
  • ♨️ Condensers and boilers too

How to use the NTU-Effectiveness Calculator

  1. 1. Pick the problemRating (area known, find outlets) or sizing (target outlet, find area).
  2. 2. Choose the exchangerCounter, parallel, shell and tube, three cross-flow cases, or phase change.
  3. 3. Enter the fluidsInlet temperatures, flow rates, cp and U to get the full answer.

ε-NTU method

Capacity rates are C = ṁ·cp for each fluid. With Cmin the smaller one and Cr = Cmin/Cmax:

  • NTU = UA / Cmin
  • Qmax = Cmin (Th,in − Tc,in) and Q = ε·Qmax
  • Counter flow: ε = [1 − e^(−NTU(1−Cr))] / [1 − Cr·e^(−NTU(1−Cr))]
  • Parallel flow: ε = [1 − e^(−NTU(1+Cr))] / (1 + Cr)
  • Boiling or condensing (Cr = 0): ε = 1 − e^(−NTU) for every type

The shell and tube and cross-flow relations are the standard ones in Cengel's tables. For sizing, the tool uses the inverse relation (or a numerical solve for the both-unmixed cross-flow case) to get NTU from ε.

Worked example and exam tips

Oil (0.5 kg/s, cp 2.1) at 150 °C is cooled by water (0.4 kg/s, cp 4.18) at 20 °C in a 5 m² counter-flow exchanger with U = 300 W/m²K. Ch = 1.05 kW/K = Cmin, Cc = 1.672 kW/K, so Cr = 0.628 and NTU = 1500 / 1050 = 1.43. This gives ε = 0.653, so Q = 0.653 × 1.05 × 130 = 89.2 kW. The oil leaves at 65 °C and the water at 73 °C.

  • Qmax always uses Cmin, never Cmax.
  • A parallel-flow exchanger can never pass ε = 1/(1 + Cr), however large it is.
  • Check your answer: ṁcpΔT must be the same Q for both fluids.

Frequently asked questions

What is effectiveness?

The actual heat transfer divided by the largest heat transfer the inlet temperatures allow. It runs from 0 to 1.

What does NTU mean physically?

NTU measures the size of the exchanger compared with the smaller capacity rate. A larger NTU means more area per unit of flow.

Why does phase change give Cr = 0?

A boiling or condensing fluid stays at a constant temperature, so it behaves as if its capacity rate were infinite.