#1 India's Top IT Training Institute
×

About Uncodemy

Know more about who we are and what we stand for.

About Us

About Us

Discover our mission to equip individuals with essential IT skills and industry expertise.

Read More →
UnCodeMy Gallery

UnCodeMy Gallery

Explore highlights from our IT training sessions and success stories.

Read More →
Mentors

Mentors

Meet the industry experts who train and guide you through your course.

Read More →
Free Resources

Free Resources

Free tutorials, interview questions, tools and calculators to help you learn.

Explore →
×

Free Resources

Learn, practice and plan your career — bilkul free.

Tutorials

Tutorials

Step-by-step written tutorials to learn any technology at your own pace.

Read More →
Free Counselling

Free Counselling

Book a free video counselling session and pick the right course for you.

Read More →
Online Compiler

Online Compiler

Write, run and test your code online — no setup required.

Read More →
⚡ FREE · STEP-BY-STEP

PID Tuning Calculator: Ziegler-Nichols Step by Step

Get P, PI and PID settings from Ku and Tu, from G(s) directly, or from a reaction-curve test.

  • 🎛️ 3 Z-N tuning methods
  • 🧮 Ku from G(s) automatically
  • 📋 P, PI, PD, PID table

How to use the PID Controller Tuning Calculator

  1. 1. Choose a methodUltimate gain (Ku, Tu), plant G(s), or reaction curve (K, L, T).
  2. 2. Enter the dataFor example G(s) = 1/(s(s+1)(s+5)).
  3. 3. Get the gainsKp, Ti and Td in ideal and parallel forms for every rule.

Ziegler-Nichols tuning methods

Second method (ultimate gain): with only proportional control, raise K until the loop oscillates steadily. That gain is Ku and the period is Tu. The classic PID settings are Kp = 0.6Ku, Ti = 0.5Tu and Td = 0.125Tu. From a transfer function, Ku and ωu come from putting s = jω in D(s) + K·N(s) = 0, which gives the same answer as the Routh array. First method (reaction curve): an open-loop step test gives the gain K, dead time L and time constant T, and the PID settings are Kp = 1.2T/(KL), Ti = 2L and Td = 0.5L.

Worked example (Ogata): G(s) = 1/(s(s+1)(s+5)). The characteristic equation is s³ + 6s² + 5s + K = 0. The imaginary part 5ω − ω³ = 0 gives ωu = √5 = 2.236 rad/s, and the real part gives Ku = 6ω² = 30. Then Tu = 2π/√5 = 2.81 s, Kp = 18, Ti = 1.405 s and Td = 0.351 s, so Gc(s) = 6.32(s + 1.4235)²/s.

Exam tips

  • The ideal form is Kp(1 + 1/(Ti·s) + Td·s). The parallel form is Kp + Ki/s + Kd·s, with Ki = Kp/Ti and Kd = Kp·Td.
  • A second-order plant without delay never oscillates under P control, so the ultimate gain method does not apply.
  • Z-N settings usually give around 25% overshoot. The 'some overshoot' and 'no overshoot' rules are gentler.
  • Always state which form your gains are in.

Frequently asked questions

How does the tool find Ku from G(s)?

It puts s = jω in 1 + K·G(s) = 0 and solves the imaginary part for ω, then the real part for K. The smallest positive K is Ku, and Tu = 2π/ω.

Which Ziegler-Nichols table is used?

The classic tables from Ziegler and Nichols (1942), plus the commonly used Pessen, 'some overshoot' and 'no overshoot' variants for the ultimate gain method.

Are these the final controller settings?

Treat them as a starting point. Fine-tune on the real plant or in a simulation to get the response you need.