#1 India's Top IT Training Institute
×

About Uncodemy

Know more about who we are and what we stand for.

About Us

About Us

Discover our mission to equip individuals with essential IT skills and industry expertise.

Read More →
UnCodeMy Gallery

UnCodeMy Gallery

Explore highlights from our IT training sessions and success stories.

Read More →
Mentors

Mentors

Meet the industry experts who train and guide you through your course.

Read More →
Free Resources

Free Resources

Free tutorials, interview questions, tools and calculators to help you learn.

Explore →
×

Free Resources

Learn, practice and plan your career — bilkul free.

Tutorials

Tutorials

Step-by-step written tutorials to learn any technology at your own pace.

Read More →
Free Counselling

Free Counselling

Book a free video counselling session and pick the right course for you.

Read More →
Online Compiler

Online Compiler

Write, run and test your code online — no setup required.

Read More →
⚡ FREE · STEP-BY-STEP

Power Factor Correction Calculator: kVAR and µF

Size a capacitor bank to improve power factor and see the current drop.

  • 🔋 Capacitor kVAR
  • 🧲 µF per phase
  • 📉 Current before and after

How to use the Power Factor Correction Calculator

  1. 1. Enter the loadActive power in kW and the present power factor.
  2. 2. Set the targetTarget pf, supply type, voltage and frequency.
  3. 3. Get the bank sizekVAR, capacitance per phase and the reduction in current.

Power factor correction formula

The active power P stays the same; capacitors supply part of the reactive power. The capacitor rating is Qc = P (tan φ1 − tan φ2), where φ1 = cos⁻¹(pf now) and φ2 = cos⁻¹(target pf).

  • Single phase: C = Qc / (2πf V²)
  • Three-phase delta bank: C = Qc / (3 × 2πf VL²) per phase
  • Three-phase star bank: C = Qc / (2πf VL²) per phase

Worked example: a 100 kW load at pf 0.7 is to be raised to 0.95. tan φ1 = 1.020 and tan φ2 = 0.329, so Qc = 100 × 0.691 = 69.2 kVAR. For a delta bank at 415 V, 50 Hz, C = 69,152 / (3 × 314.16 × 415²) = 426 µF per phase. Line current falls from 199 A to 146 A.

Why it matters and exam questions

A low power factor draws more current for the same useful power, so cables, transformers and switchgear run hotter and losses rise as I²R. Supply companies may charge extra for low power factor, so check your tariff.

  • Find the kVAR needed to raise pf from 0.6 to 0.9 for a 5 kW single-phase load (4.25 kVAR).
  • Find the capacitance per phase for star and delta banks.
  • Compare kVA before and after correction.
  • Why are delta banks smaller in µF than star banks?

Frequently asked questions

Why does a delta bank need less capacitance?

Each delta capacitor sees the full line voltage, while a star capacitor sees VL/√3. Reactive power goes with V², so delta needs one third of the µF.

Should I correct to unity power factor?

Usually not. Correcting to about 0.95 to 0.98 gets most of the benefit, and going to 1 or leading can cause over-voltage at light load.

Does correction reduce my kWh?

Not much. kWh depends on active power. Correction mainly reduces current, kVA demand and losses in cables.