#1 India's Top IT Training Institute
×

About Uncodemy

Know more about who we are and what we stand for.

About Us

About Us

Discover our mission to equip individuals with essential IT skills and industry expertise.

Read More →
UnCodeMy Gallery

UnCodeMy Gallery

Explore highlights from our IT training sessions and success stories.

Read More →
Mentors

Mentors

Meet the industry experts who train and guide you through your course.

Read More →
Free Resources

Free Resources

Free tutorials, interview questions, tools and calculators to help you learn.

Explore →
×

Free Resources

Learn, practice and plan your career — bilkul free.

Tutorials

Tutorials

Step-by-step written tutorials to learn any technology at your own pace.

Read More →
Free Counselling

Free Counselling

Book a free video counselling session and pick the right course for you.

Read More →
Online Compiler

Online Compiler

Write, run and test your code online — no setup required.

Read More →
⚡ FREE · STEP-BY-STEP

Transformer Efficiency Calculator: η, ηmax, Regulation

Use open-circuit and short-circuit test losses to get efficiency at any load.

  • 🔌 Efficiency at any load
  • 🏔️ Maximum efficiency point
  • 📏 Voltage regulation

How to use the Transformer Efficiency & Regulation Calculator

  1. 1. Enter the rating and losseskVA, core (iron) loss and full-load copper loss.
  2. 2. Set the loadLoad as % of full load, power factor and lagging/leading.
  3. 3. See the resultsEfficiency, load at maximum efficiency, regulation and a load table.

Transformer efficiency formula

At a fraction x of full load, output = x S cos φ, core loss Pi stays constant and copper loss is x² Pcu. So η = x S cos φ / (x S cos φ + Pi + x² Pcu). Maximum efficiency occurs when copper loss equals core loss, at x = √(Pi / Pcu).

Worked example: 25 kVA, Pi = 350 W, Pcu = 400 W, pf 0.8. At full load: η = 20,000 / (20,000 + 350 + 400) = 96.39%. At half load: η = 10,000 / (10,000 + 350 + 100) = 95.69%. Maximum efficiency is at x = √(350/400) = 0.935, that is 23.4 kVA, with η = 96.39%.

Voltage regulation and exam questions

Approximate regulation is x (εr cos φ ± εx sin φ) in percent, using + for lagging and − for leading loads. εr = Pcu / S × 100 comes from the copper loss, and εx is the leakage reactance in percent. In the example, εr = 1.6% and with εx = 4% at pf 0.8 lagging, regulation is 1.6 × 0.8 + 4 × 0.6 = 3.68%.

  • Find efficiency at full and half load at unity and 0.8 pf.
  • Find the kVA at which efficiency is maximum.
  • Find the regulation at a leading power factor (it can be negative).
  • Find copper loss at 75% load from the full-load value.

Frequently asked questions

Why does copper loss go with the square of load?

Copper loss is I²R, and current is proportional to load. At half load the current halves, so the copper loss falls to one quarter.

Why is regulation negative at leading pf?

With a leading load, the reactive drop can raise the secondary voltage above its no-load value, so the regulation formula gives a negative number.

Where do Pi and Pcu come from?

Pi comes from the open-circuit test at rated voltage. Pcu at full load comes from the short-circuit test at rated current.